Damper actuator for operating air control dampers in ventilation and air-conditioning systems for
building services installations
• For air control dampers up to approx. 4 m2
• Torque 20 Nm
• Nominal voltage AC/DC 24 V
• Control: modulating DC 0 ... 10 V, position feedback DC 2 ... 10 V Technische Daten
Electrical data Nominal voltage AC 24 V, 50/60 Hz
DC 24 V
Nominal voltage range AC/DC 19.2 ... 28.8 V
Power consumption In operation
At rest
For wire sizing
2 W @ nominal torque
0.4 W
4 VA
Connection Cable 1 m, 4 x 0.75 mm2
Functional data Torque (nominal torque) Min. 20 Nm @ nominal voltage
Control Control signal Y
Working range
DC 0 ... 10 V, typical input impedance 100 kΩ
DC 2 ... 10 V
Position feedback (Measuring voltage) DC 2 ... 10 V, max. 1 mA
Position accuracy ±5%
Direction of rotation Reversible with switch 0 / 1
Direction of rotation at Y = 0 V at switch position 0 resp. 1
Manual override Gearing latch disengaged with pushbutton,
self-resetting
Angle of rotation Max. 95° , limited on both sides
by means of adjustable, mechanical end stops
Running time 150 s
Sound power level Max. 45 dB (A)
Position indication Mechanical, pluggable
Safety Protection class III Safety extra-low voltage
Degree of protection IP54 in any mounting position
EMC CE according to 89/336/EEC
Mode of operation Type 1 (to EN 60730-1)
Ambient temperature range –30 ... +50°C
Non-operating temperature –40 ... +80°C
Ambient humidity range 95% r.H., non-condensating (EN 60730-1)
Maintenance Maintenance-free
Dimensions / Weight Dimensions See «Dimensions» on page 2
Weight Approx. 1’050 g
Safety notes
The damper actuator is not allowed to be used outside the specified field of applica tion,
especially in aircraft or any other form of air transport.
• Assembly must be carried out by trained personnel. Any legal regulations or regulations
issued by authorities must be observed during assembly.
• The device may only be opened at the manufacturer‘s site. It does not contain any parts
that can be replaced or repaired by the user.
• The cable must not be removed from the device.
• When calculating the required torque, the specifications supplied by the damper
manufacturers (cross section, design, installation site), and the air flow conditions must
be observed.
• The device contains electrical and electronic components and is not allowed to be disposed
of as household refuse. All locally valid regulations and requirements must be observed.
Modulating damper actuator AC/DC 24 V, 20 Nm
Product features
Mode of operation The actuator is controlled by means of a standard control signal DC 0 ... 10 V. It opens to the
position dictated by this signal. The measuring voltage U allows the damper position (0 ... 100%)
to be electrically indicated and serves as a follow-up control signal for other actuators.
Simple direct mounting Simple direct mounting on the damper spindle with a universal spindle clamp, supplied with
an anti-rotation strap to prevent the actuator from rotating.
Manual override Manual operation is possible with the self-resetting pushbutton (the gearing latch remains
disengaged as long as the pushbutton is pressed).
Adjustable angle of rotation Adjustable angle of rotation with mechanical end stops.
High functional reliability The actuator is overload-proof, requires no limit switches and automatically stops when the
end stop is reached.
Accessories
Description Data sheet
Electrical accessories Auxiliary switch S..A.. T2 - S..A..
Feedback potentiometer P..A.. T2 - P..A..
Range controller SBG24 T2 - SBG24
Positioner SG..24 T2 - SG..24
Digital position indication ZAD24 T2 - ZAD24
Mechanical accessories Various accessories (clamps, shaft extensions etc.) T2 - Z-SM..A..
Electrical installation
Wiring diagrams
Y
U
1 2 3 5
DC 0…10 V
DC 2…10 V
– +
~ T
Dimensions [mm]
Dimensional drawings
139
56
64
30 109 41
88
Damper spindle Length
Clamp on top min. 42 10 ... 20 (26.7)
Clamp on bottom min. 20 10 ... 20
Notes
• Connection via safety isolating transformer.
• Other actuators can be connected in parallel.
Please note the performance data.
![]() |
![]() |